Type: | Water-Cooled |
---|---|
Cooling Method: | Water-cooled |
Unit Structure: | Integral |
Selected Voltage: | 220V/380V/400V/415V/440V-3pH-50Hz/60Hz |
Compressor Number: | 1 or 2 |
Noise Level: | Low |
Lieferanten mit verifizierten Geschäftslizenzen
Wassergekühlte Niedertemperatur-Schraubenkühlung (Wärmerückgewinnung ) (0ºC/R22) | |||||||||||||
Modell ESGI | 020DSOBS | 030DSOBS | 035DSOBS | 050DSOBS | 055DSOBS | 060DSOBS | 070DSOBS | 080DSOBS | 085DSOBS | 100DSOBS | 120DSOBS | 130DSOBS | |
020DSOBVS | 030DSOBVS | 035DSOBVS | 050DSOBVS | 055DSOBVS | 060DSOBVS | 070DSOBVS | 080DSOBVS | 085DSOBVS | 100DSOBVS | 120DSOBVS | 130DSOBVS | ||
Nennkühlleistung | KW | 71 | 97 | 127 | 169 | 185 | 219 | 253 | 274 | 301 | 359 | 414 | 449 |
USRT | 20, 2 | 27, 6 | 36, 2 | 48, 0 | 52, 7 | 62, 2 | 71, 9 | 77, 8 | 85, 6 | 101, 9 | 117, 8 | 127, 6 | |
X1000 Kcal/h | 61, 0 | 83, 3 | 109, 5 | 145, 1 | 159, 4 | 188, 0 | 217, 3 | 235, 2 | 258, 9 | 308, 3 | 356, 3 | 386, 0 | |
Eingangsleistung | KW | 22, 4 | 29, 3 | 36, 6 | 48, 8 | 53, 2 | 59, 5 | 68, 9 | 75, 3 | 83, 8 | 97, 0 | 110, 9 | 119, 2 |
Kpl. Eingangsleistung XQTY (kw) | 22.4X1 | 29, 3X1 | 36, 6X1 | 48, 8X1 | 53, 2X1 | 59, 5X1 | 68, 9X1 | 75, 3X1 | 83, 8X1 | 97.0X1 | 110, 9×1 | 119, 2×1 | |
Kompr. Strom (A) | 37, 6 | 49, 3 | 61, 5 | 82, 1 | 89, 4 | 100, 1 | 115, 9 | 126, 5 | 140, 9 | 163, 1 | 186, 4 | 200, 4 | |
Stromversorgung /Kältemittel | 3 -380V-50HZ/R22 | ||||||||||||
Schutzvorrichtung | Phasenumkehr -Schutz, Phasenmangelschutz , Überlaststromschutz , Schutz vor Ablufttemperatur , Nieder- und Hochdruck , Schutz vor niedriger Temperatur, Schnittstelle für reservierten Wasserdurchflussschutz . |
||||||||||||
Anzahl Kühlkreislauf | 1 | ||||||||||||
Kapazitätskontrolle (%) | 0, 66, 100 | 0, 50, 75, 100 | |||||||||||
Kältemittelfüllung (kg) | 18 | 25 | 32 | 42 | 46 | 55 | 62 | 68 | 75 | 90 | 102 | 110 | |
Kondensator | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr -Kondensator (Zoll) | 2 Zoll | 2-1/2“ | 3 Zoll | 3 Zoll | 3 Zoll | 3 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | |
Kühlwasserdurchfluss (m3/h) | 16, 1 | 21, 7 | 28, 2 | 37, 4 | 41, 0 | 47, 8 | 55, 3 | 60, 0 | 66, 2 | 78, 3 | 90, 3 | 97, 7 | |
Wasserdruckabfall des Kondensators (kPa) | 39 | 45 | 43 | 50 | 50 | 49 | 47 | 48 | 48 | 49 | 48 | 49 | |
Verdampfer | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr Zum Verdampfer (Zoll) | 2 Zoll | 2-1/2“ | 3 Zoll | 3 Zoll | 3 Zoll | 3 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 5 Zoll | 5 Zoll | |
20 % Glykol -Durchflusskapazität (m3/h) | 12, 9 | 17, 6 | 23, 2 | 30, 7 | 33, 7 | 39, 8 | 46, 0 | 49, 8 | 54, 8 | 65, 2 | 75, 4 | 81, 7 | |
Wasserdruckabfall Verdampfer (kPa) | 24 | 31 | 35 | 39 | 50 | 49 | 47 | 73 | 70 | 47 | 52 | 69 | |
Laufgeräusche DB(A) | 73, 1 | 73, 7 | 74, 8 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | |
Gesamtgewicht (kg) | 980 | 1010 | 1200 | 1350 | 1540 | 1680 | 1800 | 1920 | 2030 | 2080 | 2520 | 2730 | |
Laufgewicht (Kg) | 1080 | 1120 | 1360 | 1530 | 1700 | 1850 | 1980 | 2080 | 2240 | 2660 | 2800 | 3020 | |
Parameter Für Die Wärmerückgewinnung | |||||||||||||
Kältemittelfüllung (kg) | 21 | 28 | 35 | 45 | 49 | 58 | 65 | 71 | 78 | 95 | 107 | 115 | |
Volumen Der Zurückgewonnenen Wärme | KW | 21 | 29 | 38 | 51 | 56 | 66 | 76 | 82 | 90 | 108 | 124 | 135 |
USRT | 6, 1 | 8, 3 | 10, 9 | 14, 4 | 15, 8 | 18, 6 | 21, 6 | 23, 3 | 25, 7 | 30, 6 | 35, 3 | 38, 3 | |
X1000 Kcal/h | 18, 3 | 25, 0 | 32, 8 | 43, 5 | 47, 8 | 56, 4 | 65, 2 | 70, 6 | 77, 7 | 92, 5 | 106, 9 | 115, 8 | |
Wärmerücksteller | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr Zu Wärmerücksteller (Zoll) | 1 Zoll | 1-1/2“ | 1-1/2“ | 1-1/2“ | 1-1/2“ | 2 Zoll | 2 Zoll | 2 Zoll | 2 Zoll | 2 Zoll | 2-1/2“ | 2-1/2“ | |
Rücklaufwasserstrom (m3/h) | 3, 7 | 5, 0 | 6, 6 | 8, 7 | 9, 6 | 11, 3 | 13, 0 | 14, 1 | 15, 5 | 18, 5 | 21, 4 | 23, 2 | |
Wärmerückgewinnungseinheit Wasser Druckabfall (kPa) |
21 | 24 | 23 | 24 | 27 | 27 | 26 | 26 | 26 | 26 | 27 | 26 | |
Gesamtgewicht (kg) | 1030 | 1060 | 1250 | 1400 | 1590 | 1730 | 1880 | 2020 | 2110 | 2460 | 2620 | 2830 | |
Laufgewicht (Kg) | 1130 | 1170 | 1410 | 1580 | 1750 | 1900 | 2060 | 2160 | 2320 | 2740 | 2900 | 3120 |
Wassergekühlte Niedertemperatur-Schraubenkühlung (Wärmerückgewinnung ) (0ºC/R22) | |||||||||||||
Modell ESGI | 135DSOBS | 155DSOBS | 170DSOBS | 180DSOBS | 205DSOBS | 250DSOBS | 295DSOBS | 335DSOBS | 040DDOBS | 095DDOBS | 105DDOBS | 145DDOBS | |
135DSOBVS | 155DSOBVS | 170DSOBVS | 180DSOBVS | 205DSOBVS | 250DSOBVS | 295DSOBVS | 335DSOBVS | 040DDOBVS | 095DDOBVS | 105DDOBVS | 145DDOBVS | ||
Nennkühlleistung | KW | 466 | 543 | 596 | 637 | 718 | 880 | 1036 | 1184 | 142 | 338 | 371 | 505 |
USRT | 132, 6 | 154, 4 | 169, 5 | 181, 0 | 204, 0 | 250, 1 | 294, 7 | 336, 7 | 40, 4 | 96, 0 | 105, 4 | 143, 7 | |
X1000 Kcal/h | 400, 9 | 466, 9 | 512, 7 | 547, 4 | 617, 0 | 756, 3 | 891, 1 | 1018, 3 | 122, 1 | 290, 3 | 318, 8 | 434, 6 | |
Eingangsleistung | KW | 123, 0 | 141, 7 | 157, 2 | 166, 9 | 187, 7 | 229, 0 | 268, 3 | 303, 5 | 44, 8 | 97, 6 | 106, 4 | 137, 8 |
Kpl. Eingangsleistung XQTY (kw) | 123, 0×1 | 141, 7×1 | 157, 2×1 | 166, 9×1 | 187, 7×1 | 229, 0×1 | 268, 3×1 | 303, 5×1 | 22, 4×2 | 48, 8×2 | 53, 2×2 | 68, 9×2 | |
Kompr. Strom (A) | 206, 7 | 238, 2 | 264, 2 | 280, 6 | 315, 5 | 385, 0 | 451, 1 | 510, 3 | 75, 2 | 164, 2 | 178, 8 | 231, 8 | |
Stromversorgung /Kältemittel | 3 -380V-50HZ/R22 | ||||||||||||
Schutzvorrichtung | Phasenumkehr -Schutz, Phasenmangelschutz , Überlaststromschutz , Schutz vor Ablufttemperatur , Nieder- und Hochdruck , Schutz vor niedriger Temperatur, Schutzschnittstelle für reservierten Wasserdurchfluss . |
||||||||||||
Anzahl Kühlkreislauf | 1 | 2 | |||||||||||
Kapazitätskontrolle (%) | 0, 50, 75, 100 | 0, 25, 37, 5, 50, 62, 5, 75, 87.5, 100 | |||||||||||
Kältemittelfüllung (kg) | 115 | 134 | 148 | 158 | 177 | 218 | 256 | 292 | 36 | 84 | 92 | 124 | |
Kondensator | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr -Kondensator (Zoll) | 5 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | 6 Zoll | 6 Zoll | 8 Zoll | 8 Zoll | 3 Zoll | 4 Zoll | 5 Zoll | 5 Zoll | |
Kühlwasserdurchfluss (m3/h) | 101, 3 | 117, 7 | 129, 6 | 138, 2 | 155, 7 | 190, 6 | 224, 4 | 255, 9 | 32, 1 | 74, 8 | 82, 1 | 110, 6 | |
Wasserdruckabfall des Kondensators (kPa) | 55 | 62 | 64 | 65 | 67 | 70 | 80 | 84 | 42 | 45 | 46 | 47 | |
Verdampfer | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr Zum Verdampfer (Zoll) | 5 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 3 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | |
20 % Glykol -Durchflusskapazität (m3/h) | 84, 8 | 98, 8 | 108, 5 | 115, 8 | 130, 6 | 160, 1 | 188, 6 | 215, 5 | 25, 8 | 61, 4 | 67, 5 | 92, 0 | |
Wasserdruckabfall Verdampfer (kPa) | 87 | 44 | 64 | 76 | 79 | 81 | 84 | 87 | 34 | 47 | 59 | 49 | |
Laufgeräusche DB(A) | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | |
Gesamtgewicht (kg) | 2820 | 2980 | 3220 | 3400 | 3680 | 4150 | 4420 | 4780 | 1570 | 2510 | 2820 | 3250 | |
Laufgewicht (Kg) | 3240 | 3400 | 3750 | 4000 | 4250 | 4730 | 5020 | 5380 | 1990 | 3300 | 3700 | 4350 | |
Parameter Für Die Wärmerückgewinnung | |||||||||||||
Kältemittelfüllung (kg) | 120 | 140 | 154 | 164 | 185 | 228 | 266 | 306 | 42 | 90 | 98 | 130 | |
Volumen Der Zurückgewonnenen Wärme | KW | 140 | 163 | 179 | 191 | 215 | 264 | 311 | 355 | 43 | 101 | 111 | 152 |
USRT | 39, 8 | 46, 3 | 50, 9 | 54, 3 | 61, 2 | 75, 0 | 88, 4 | 101, 0 | 12, 1 | 28, 8 | 31, 6 | 43, 1 | |
X1000 Kcal/h | 120, 3 | 140, 1 | 153, 8 | 164, 2 | 185, 1 | 226, 9 | 267, 3 | 305, 5 | 36, 6 | 87, 1 | 95, 6 | 130, 4 | |
Wärmerücksteller | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr Zu Wärmerücksteller (Zoll) | 2-1/2“ | 3 Zoll | 3 Zoll | 3 Zoll | 3 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 2 Zoll | 2-1/2“ | 2-1/2“ | 2-1/2“ | |
Rücklaufwasserstrom (m3/h) | 24, 1 | 28, 0 | 30, 8 | 32, 8 | 37, 0 | 45, 4 | 53, 5 | 61, 1 | 7, 3 | 17, 4 | 19, 1 | 26, 1 | |
Wärmerückgewinnungseinheit Wasser Druckabfall (kPa) |
26 | 26 | 27 | 30 | 32 | 34 | 35 | 35 | 23 | 26 | 26 | 28 | |
Gesamtgewicht (kg) | 2920 | 3080 | 3320 | 3500 | 3780 | 4710 | 5080 | 5470 | 1720 | 2790 | 3120 | 3700 | |
Laufgewicht (Kg) | 3340 | 3500 | 3850 | 4100 | 4350 | 5320 | 5700 | 6100 | 2170 | 3600 | 3980 | 4750 |
Wassergekühlte Niedertemperatur-Schraubenkühlung (Wärmerückgewinnung ) (0ºC/R22) | ||||||||||||
Modell ESGI | 215DDOBS | 235DDOBS | 255DDOBS | 265DDOBS | 310DDOBS | 340DDOBS | 360DDOBS | 410DDOBS | 500DDOBS | 590DDOBS | 675DDOBS | |
215DDOBVS | 235DDOBVS | 255DDOBVS | 265DDOBVS | 310DDOBVS | 340DDOBVS | 360DDOBS | 410DDOBVS | 500DDOBVS | 590DDOBVS | 675DDOBVS | ||
Nennkühlleistung | KW | 757 | 829 | 898 | 932 | 1086 | 1193 | 1273 | 1435 | 1759 | 2073 | 2369 |
USRT | 215, 3 | 235, 7 | 255, 3 | 265, 1 | 308, 8 | 339, 1 | 362, 0 | 408, 1 | 500, 2 | 589, 4 | 673, 5 | |
X1000 Kcal/h | 651, 0 | 712, 6 | 772, 0 | 801, 7 | 933, 8 | 1025, 5 | 1094, 8 | 1234, 0 | 1512, 6 | 1782, 3 | 2036, 6 | |
Eingangsleistung | KW | 204, 8 | 221, 8 | 238, 4 | 246, 0 | 283, 4 | 314, 4 | 333, 8 | 375, 4 | 458, 0 | 536, 6 | 607, 0 |
Kpl. Eingangsleistung XQTY (kw) | 102, 4×2 | 110, 9×2 | 119, 2×2 | 123, 0×2 | 141, 7×2 | 157, 2×2 | 166, 9×2 | 187, 7×2 | 229, 0×2 | 268, 3×2 | 303, 5×2 | |
Kompr. Strom (A) | 344, 4 | 372, 8 | 400, 8 | 413, 4 | 476, 4 | 528, 4 | 561, 2 | 631, 0 | 770, 0 | 902, 2 | 1020, 6 | |
Stromversorgung /Kältemittel | 3 -380V-50HZ/R22 | |||||||||||
Schutzvorrichtung | Phasenumkehr -Schutz, Phasenmangelschutz , Überlaststromschutz , Schutz vor Ablufttemperatur , Nieder- und Hochdruck , Schutz vor niedriger Temperatur, Schutzschnittstelle für reservierten Wasserdurchfluss . |
|||||||||||
Anzahl Kühlkreislauf | 2 | |||||||||||
Kapazitätskontrolle (%) | 0, 25, 37, 5, 50, 62, 5, 75, 87.5, 100 | |||||||||||
Kältemittelfüllung (kg) | 188 | 204 | 220 | 230 | 268 | 296 | 316 | 354 | 436 | 512 | 584 | |
Kondensator | Gehäuse - und Rohrtyp | |||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | |||||||||||
Durchmesser Rohr -Kondensator (Zoll) | 4 x 2 cm | 5 x 2 cm | 5 x 2 cm | 5 x 2 cm | 5 x 2 cm | 5 x 2 cm | 5 Zoll X2 | 6 Zoll X2 | 6 Zoll X2 | 8 Zoll X2 | 8 Zoll X2 | |
Kühlwasserdurchfluss (m3/h) | 165, 4 | 180, 7 | 195, 4 | 202, 6 | 235, 5 | 259, 2 | 276, 4 | 311, 4 | 381, 3 | 448, 7 | 511, 7 | |
Wasserdruckabfall des Kondensators (kPa) | 48 | 49 | 52 | 55 | 62 | 64 | 70 | 77 | 80 | 83 | 89 | |
Verdampfer | Gehäuse - und Rohrtyp | |||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | |||||||||||
Durchmesser Rohr Zum Verdampfer (Zoll) | 6 Zoll | 6 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 10 Zoll | 10 Zoll | |
20 % Glykol -Durchflusskapazität (m3/h) | 137, 8 | 150, 8 | 163, 4 | 169, 7 | 197, 6 | 217, 0 | 231, 7 | 261, 2 | 320, 1 | 377, 2 | 431, 0 | |
Wasserdruckabfall Verdampfer (kPa) | 52 | 58 | 57 | 61 | 66 | 86 | 83 | 80 | 77 | 85 | 92 | |
Laufgeräusche DB(A) | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | |
Gesamtgewicht (kg) | 4150 | 4390 | 4800 | 5340 | 5850 | 6310 | 6540 | 6790 | 8200 | 8900 | 9500 | |
Laufgewicht (Kg) | 5370 | 5710 | 6150 | 6390 | 6630 | 6880 | 7220 | 7570 | 9360 | 10200 | 10800 | |
Parameter Für Die Wärmerückgewinnung | ||||||||||||
Kältemittelfüllung (kg) | 196 | 214 | 230 | 240 | 280 | 308 | 328 | 370 | 456 | 532 | 612 | |
Volumen Der Zurückgewonnenen Wärme | KW | 227 | 249 | 269 | 280 | 326 | 358 | 382 | 431 | 528 | 622 | 711 |
USRT | 64, 6 | 70, 7 | 76, 6 | 79, 5 | 92, 6 | 101, 7 | 108, 6 | 122, 4 | 150, 1 | 176, 8 | 202, 0 | |
X1000 Kcal/h | 195, 3 | 213, 8 | 231, 6 | 240, 5 | 280, 1 | 307, 6 | 328, 4 | 370, 2 | 453, 8 | 534, 7 | 611, 0 | |
Wärmerücksteller | Gehäuse - und Rohrtyp | |||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | |||||||||||
Durchmesser Rohr Zu Wärmerücksteller (Zoll) | 3 Zoll | 3 Zoll | 3 Zoll | 3 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | |
Rücklaufwasserstrom (m3/h) | 39, 1 | 42, 8 | 46, 3 | 48, 1 | 56, 0 | 61, 5 | 65, 7 | 74, 0 | 90, 8 | 106, 9 | 122, 2 | |
Wärmerückgewinnungseinheit Wasser Druckabfall (kPa) |
34 | 35 | 38 | 38 | 39 | 42 | 43 | 43 | 43 | 43 | 43 | |
Gesamtgewicht (kg) | 4340 | 4970 | 5460 | 5950 | 6470 | 6990 | 7350 | 7600 | 8450 | 9380 | 9980 | |
Laufgewicht (Kg) | 5520 | 6290 | 6580 | 6840 | 7190 | 7540 | 8020 | 8270 | 9620 | 10580 | 11200 |
Wassergekühlte Niedertemperatur-Schraubenkühlung (Wärmerückgewinnung ) (0ºC/R404A) | |||||||||||||
Modell ESGI | 020DSOBY | 025DSOBY | 035DSOBY | 045DSOBY | 050DSOBY | 060DSOBY | 070DSOBY | 075DSOBY | 080DSOBY | 095DSOBY | 115DSOBY | 120DSOBY | |
020DSOBVY | 025DSOBVY | 035DSOBVY | 045DSOBVY | 050DSOBVY | 060DSOBVY | 070DSOBVY | 075DSOBVY | 080DSOBVY | 095DSOBVY | 115DSOBVY | 120DSOBVY | ||
Nennkühlleistung | KW | 70 | 93 | 121 | 161 | 180 | 208 | 241 | 265 | 286 | 340 | 397 | 423 |
USRT | 19, 9 | 26, 4 | 34, 4 | 45, 8 | 51, 2 | 59, 1 | 68, 5 | 75, 3 | 81, 3 | 96, 7 | 112, 9 | 120, 3 | |
X1000 Kcal/h | 60, 2 | 80, 0 | 104, 0 | 138, 4 | 154, 8 | 178, 8 | 207, 2 | 227, 9 | 245, 9 | 292, 3 | 341, 4 | 363, 7 | |
Eingangsleistung | KW | 25, 0 | 32, 8 | 41, 7 | 54, 5 | 61, 3 | 69, 8 | 80, 7 | 87, 8 | 96, 2 | 113, 6 | 133, 4 | 141, 5 |
Kpl. Eingangsleistung XQTY (kw) | 25, 0×1 | 32, 8×1 | 41, 7×1 | 54, 5×1 | 61, 3×1 | 69, 8×1 | 80, 7×1 | 87, 8×1 | 96, 2×1 | 113, 6×1 | 133, 4×1 | 141, 5×1 | |
Kompr. Strom (A) | 42, 1 | 55, 1 | 70, 1 | 91, 7 | 103, 1 | 117, 4 | 135, 7 | 147, 6 | 161, 7 | 191, 0 | 224, 3 | 237, 8 | |
Stromversorgung /Kältemittel | 3 -380V-50HZ/R404A | ||||||||||||
Schutzvorrichtung | Phasenumkehr -Schutz, Phasenmangelschutz , Überlaststromschutz , Schutz vor Ablufttemperatur , Nieder- und Hochdruck , Schutz vor niedriger Temperatur, Schutzschnittstelle für reservierten Wasserdurchfluss . |
||||||||||||
Anzahl Kühlkreislauf | 1 | ||||||||||||
Kapazitätskontrolle (%) | 0, 66, 100 | 0, 50, 75, 100 | |||||||||||
Kältemittelfüllung (kg) | 18 | 25 | 32 | 42 | 46 | 55 | 62 | 68 | 75 | 90 | 102 | 110 | |
Kondensator | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr -Kondensator (Zoll) | 2 Zoll | 2-1/2“ | 3 Zoll | 3 Zoll | 3 Zoll | 3 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | |
Kühlwasserdurchfluss (m3/h) | 16, 3 | 21, 6 | 28 | 37, 1 | 41, 5 | 47, 8 | 55, 3 | 60, 7 | 65, 7 | 78, 0 | 91, 2 | 97, 1 | |
Wasserdruckabfall des Kondensators (kPa) | 39 | 45 | 43 | 50 | 50 | 49 | 47 | 48 | 48 | 49 | 48 | 49 | |
Verdampfer | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr Zum Verdampfer (Zoll) | 2 Zoll | 2-1/2“ | 3 Zoll | 3 Zoll | 3 Zoll | 3 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 5 Zoll | 5 Zoll | |
20 % Glykol -Durchflusskapazität (m3/h) | 12, 7 | 16, 9 | 22, 0 | 29, 3 | 32, 8 | 37, 9 | 43, 9 | 48, 2 | 52, 0 | 61, 9 | 72, 2 | 77, 0 | |
Wasserdruckabfall Verdampfer (kPa) | 24 | 31 | 35 | 39 | 50 | 49 | 47 | 73 | 70 | 47 | 52 | 69 | |
Laufgeräusche DB(A) | 73, 1 | 73, 7 | 74, 8 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | |
Gesamtgewicht (kg) | 980 | 1010 | 1200 | 1350 | 1540 | 1680 | 1800 | 1920 | 2030 | 2080 | 2520 | 2730 | |
Laufgewicht (Kg) | 1080 | 1120 | 1360 | 1530 | 1700 | 1850 | 1980 | 2080 | 2240 | 2660 | 2800 | 3020 | |
Parameter Für Die Wärmerückgewinnung | |||||||||||||
Kältemittelfüllung (kg) | 21 | 28 | 35 | 45 | 49 | 58 | 65 | 71 | 78 | 95 | 107 | 115 | |
Volumen Der Zurückgewonnenen Wärme | KW | 21 | 28 | 36 | 48 | 54 | 62 | 72 | 80 | 86 | 102 | 119 | 127 |
USRT | 6, 0 | 7, 9 | 10, 3 | 13, 7 | 15, 4 | 17, 7 | 20, 6 | 22, 6 | 24, 4 | 29, 0 | 33, 9 | 36, 1 | |
X1000 Kcal/h | 18, 1 | 24, 0 | 31, 2 | 41, 5 | 46, 4 | 53, 7 | 62, 2 | 68, 4 | 73, 8 | 87, 7 | 102, 4 | 109, 1 | |
Wärmerücksteller | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr Zu Wärmerücksteller (Zoll) | 1 Zoll | 1-1/2“ | 1-1/2“ | 1-1/2“ | 1-1/2“ | 2 Zoll | 2 Zoll | 2 Zoll | 2 Zoll | 2 Zoll | 2-1/2“ | 2-1/2“ | |
Rücklaufwasserstrom (m3/h) | 3, 6 | 4, 8 | 6, 2 | 8, 3 | 9, 3 | 10, 7 | 12, 4 | 13, 7 | 14, 8 | 17, 5 | 20, 5 | 21, 8 | |
Wärmerückgewinnungseinheit Wasser Druckabfall (kPa) |
21 | 24 | 23 | 24 | 27 | 27 | 26 | 26 | 26 | 26 | 27 | 26 | |
Gesamtgewicht (kg) | 1030 | 1060 | 1250 | 1400 | 1590 | 1730 | 1880 | 2020 | 2110 | 2460 | 2620 | 2830 | |
Laufgewicht (Kg) | 1130 | 1170 | 1410 | 1580 | 1750 | 1900 | 2060 | 2160 | 2320 | 2740 | 2900 | 3120 |
Wassergekühlte Niedertemperatur-Schraubenkühlung (Wärmerückgewinnung ) (0ºC/R404A) | |||||||||||||
Modell ESGI | 125DSOBY | 145DSOBY | 160DSOBY | 175DSOBY | 195DSOBY | 240DSOBY | 285DSOBY | 315DSOBY | 040DDOBY | 090DDOBY | 105DDOBY | 135DDOBY | |
125DSOBVY | 145DSOBVY | 160DSOBVY | 175DSOBVY | 195DSOBVY | 240DSOBVY | 285DSOBVY | 315DSOBVY | 040DDOBVY | 090DDOBVY | 105DDOBVY | 135DDOBVY | ||
Nennkühlleistung | KW | 443 | 515 | 565 | 607 | 678 | 849 | 1000 | 1116 | 139 | 322 | 361 | 481 |
USRT | 126, 0 | 146, 4 | 160, 6 | 172, 6 | 192, 8 | 241, 1 | 284, 3 | 317, 3 | 39, 5 | 91, 6 | 102, 6 | 136, 8 | |
X1000 Kcal/h | 380, 9 | 442, 8 | 485, 8 | 521, 9 | 583, 0 | 730, 0 | 859, 8 | 959, 6 | 119, 5 | 276, 9 | 310, 4 | 413, 6 | |
Eingangsleistung | KW | 149, 0 | 171, 7 | 188, 5 | 200, 8 | 223, 1 | 283, 9 | 332, 4 | 367, 4 | 50, 0 | 109, 0 | 122, 6 | 161, 4 |
Kpl. Eingangsleistung XQTY (kw) | 149, 0×1 | 171, 7×1 | 188, 5×1 | 200, 8×1 | 223, 1×1 | 283, 9×1 | 332, 4×1 | 367, 4×1 | 25, 0×2 | 54, 5×2 | 61, 3×2 | 80, 7×2 | |
Kompr. Strom (A) | 250, 5 | 288, 6 | 317, 0 | 337, 6 | 375, 1 | 477, 3 | 558, 9 | 617, 7 | 84, 2 | 183, 4 | 206, 2 | 271, 4 | |
Stromversorgung /Kältemittel | 3 -380V-50HZ/R404A | ||||||||||||
Schutzvorrichtung | Phasenumkehr -Schutz, Phasenmangelschutz , Überlaststromschutz , Schutz vor Ablufttemperatur , Nieder- und Hochdruck , Schutz vor niedriger Temperatur, Schutzschnittstelle für reservierten Wasserdurchfluss . |
||||||||||||
Anzahl Kühlkreislauf | 1 | 2 | |||||||||||
Kapazitätskontrolle (%) | 0, 50, 75, 100 | 0, 25, 37, 5, 50, 62, 5, 75, 87.5, 100 | |||||||||||
Kältemittelfüllung (kg) | 115 | 134 | 148 | 158 | 177 | 218 | 256 | 292 | 36 | 84 | 92 | 124 | |
Kondensator | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr -Kondensator (Zoll) | 5 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | 6 Zoll | 6 Zoll | 8 Zoll | 8 Zoll | 3 Zoll | 4 Zoll | 5 Zoll | 5 Zoll | |
Kühlwasserdurchfluss (m3/h) | 101, 8 | 118, 1 | 129, 6 | 138, 9 | 155, 0 | 194, 8 | 229, 1 | 255, 1 | 32, 5 | 74, 1 | 83, 2 | 110, 5 | |
Wasserdruckabfall des Kondensators (kPa) | 55 | 62 | 64 | 65 | 67 | 70 | 80 | 84 | 42 | 45 | 46 | 47 | |
Verdampfer | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr Zum Verdampfer (Zoll) | 5 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 3 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | |
20 % Glykol -Durchflusskapazität (m3/h) | 80, 6 | 93, 7 | 102, 8 | 110, 5 | 123, 4 | 154, 5 | 182, 0 | 203, 1 | 25, 3 | 58, 6 | 65, 7 | 87, 5 | |
Wasserdruckabfall Verdampfer (kPa) | 87 | 44 | 64 | 76 | 79 | 81 | 84 | 87 | 34 | 47 | 59 | 49 | |
Laufgeräusche DB(A) | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | |
Gesamtgewicht (kg) | 2820 | 2980 | 3220 | 3400 | 3680 | 4150 | 4420 | 4780 | 1570 | 2510 | 2820 | 3250 | |
Laufgewicht (Kg) | 3240 | 3400 | 3750 | 4000 | 4250 | 4730 | 5020 | 5380 | 1990 | 3300 | 3700 | 4350 | |
Parameter Für Die Wärmerückgewinnung | |||||||||||||
Kältemittelfüllung (kg) | 120 | 140 | 154 | 164 | 185 | 228 | 266 | 306 | 42 | 90 | 98 | 130 | |
Volumen Der Zurückgewonnenen Wärme | KW | 133 | 155 | 170 | 182 | 203 | 255 | 300 | 335 | 42 | 97 | 108 | 144 |
USRT | 37, 8 | 43, 9 | 48, 2 | 51, 8 | 57, 8 | 72, 4 | 85, 3 | 95, 2 | 11, 9 | 27, 5 | 30, 8 | 41, 0 | |
X1000 Kcal/h | 114, 3 | 132, 8 | 145, 7 | 156, 6 | 174, 9 | 219, 0 | 258, 0 | 287, 9 | 35, 9 | 83, 1 | 93, 1 | 124, 1 | |
Wärmerücksteller | Gehäuse - und Rohrtyp | ||||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | ||||||||||||
Durchmesser Rohr Zu Wärmerücksteller (Zoll) | 2-1/2“ | 3 Zoll | 3 Zoll | 3 Zoll | 3 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 2 Zoll | 2-1/2“ | 2-1/2“ | 2-1/2“ | |
Rücklaufwasserstrom (m3/h) | 22, 9 | 26, 6 | 29, 1 | 31, 3 | 35, 0 | 43, 8 | 51, 6 | 57, 6 | 7, 2 | 16, 6 | 18, 6 | 24, 8 | |
Wärmerückgewinnungseinheit Wasser Druckabfall (kPa) |
26 | 26 | 27 | 30 | 32 | 34 | 35 | 35 | 23 | 26 | 26 | 28 | |
Gesamtgewicht (kg) | 2920 | 3080 | 3320 | 3500 | 3780 | 4710 | 5080 | 5470 | 1720 | 2790 | 3120 | 3700 | |
Laufgewicht (Kg) | 3340 | 3500 | 3850 | 4100 | 4350 | 5320 | 5700 | 6100 | 2170 | 3600 | 3980 | 4750 |
Wassergekühlte Niedertemperatur-Schraubenkühlung (Wärmerückgewinnung ) (0ºC/R404A) | ||||||||||||
Modell ESGI | 205DDOBY | 225DDOBY | 240DDOBY | 250DDOBY | 295DDOBY | 320DDOBY | 345DDOBY | 385DDOBY | 485DDOBY | 570DDOBY | 635DDOBY | |
205DDOBVY | 225DDOBVY | 240DDOBVY | 250DDOBVY | 295DDOBVY | 320DDOBVY | 345DDOBVY | 385DDOBVY | 485DDOBVY | 570DDOBVY | 635DDOBVY | ||
Nennkühlleistung | KW | 718 | 795 | 847 | 886 | 1030 | 1131 | 1215 | 1356 | 1699 | 2000 | 2233 |
USRT | 204, 2 | 226, 0 | 240, 8 | 251, 9 | 292, 9 | 321, 6 | 345, 5 | 385, 6 | 483, 1 | 568, 7 | 634, 9 | |
X1000 Kcal/h | 617, 4 | 683, 6 | 728, 3 | 761, 8 | 885, 6 | 972, 5 | 1044, 7 | 1166, 0 | 1460, 9 | 1719, 7 | 1920, 0 | |
Eingangsleistung | KW | 240, 0 | 266, 8 | 283, 0 | 298, 0 | 343, 4 | 377, 0 | 401, 6 | 446, 2 | 567, 8 | 664, 8 | 734, 8 |
Kpl. Eingangsleistung XQTY (kw) | 120, 0×2 | 133, 4×2 | 141, 5×2 | 149, 0×2 | 171, 7×2 | 188, 5×2 | 200, 8 X2 | 223, 1 X2 | 283, 9 X2 | 332, 4 X2 | 367, 4 X2 | |
Kompr. Strom (A) | 403, 4 | 448, 6 | 475, 6 | 501, 0 | 577, 2 | 634, 0 | 675, 2 | 750, 2 | 954, 6 | 1117, 8 | 1235, 4 | |
Stromversorgung /Kältemittel | 3 -380V-50HZ/R404A | |||||||||||
Schutzvorrichtung | Phasenumkehr -Schutz, Phasenmangelschutz , Überlaststromschutz , Schutz vor Ablufttemperatur , Nieder- und Hochdruck , Schutz vor niedriger Temperatur, Schutzschnittstelle für reservierten Wasserdurchfluss . |
|||||||||||
Anzahl Kühlkreislauf | 2 | |||||||||||
Kapazitätskontrolle (%) | 0, 25, 37, 5, 50, 62, 5, 75, 87.5, 100 | |||||||||||
Kältemittelfüllung (kg) | 188 | 204 | 220 | 230 | 268 | 296 | 316 | 354 | 436 | 512 | 584 | |
Kondensator | Gehäuse - und Rohrtyp | |||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | |||||||||||
Durchmesser Rohr -Kondensator (Zoll) | 4 x 2 cm | 5 x 2 cm | 5 x 2 cm | 5 x 2 cm | 5 x 2 cm | 5 x 2 cm | 5 Zoll X2 | 6 Zoll X2 | 6 Zoll X2 | 8 Zoll X2 | 8 Zoll X2 | |
Kühlwasserdurchfluss (m3/h) | 164, 7 | 182, 6 | 194, 3 | 203, 6 | 236, 2 | 259, 3 | 278, 0 | 309, 9 | 389, 8 | 458, 3 | 510, 4 | |
Wasserdruckabfall des Kondensators (kPa) | 48 | 49 | 52 | 55 | 62 | 64 | 70 | 77 | 80 | 83 | 89 | |
Verdampfer | Gehäuse - und Rohrtyp | |||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | |||||||||||
Durchmesser Rohr Zum Verdampfer (Zoll) | 6 Zoll | 6 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 8 Zoll | 10 Zoll | 10 Zoll | |
20 % Glykol -Durchflusskapazität (m3/h) | 130, 7 | 144, 7 | 154, 1 | 161, 2 | 187, 4 | 205, 8 | 221, 1 | 246, 8 | 309, 2 | 364, 0 | 406, 4 | |
Wasserdruckabfall Verdampfer (kPa) | 52 | 58 | 57 | 61 | 66 | 86 | 83 | 80 | 77 | 85 | 92 | |
Laufgeräusche DB(A) | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | 75, 0 | |
Gesamtgewicht (kg) | 4150 | 4390 | 4800 | 5340 | 5850 | 6310 | 6540 | 6790 | 8200 | 8900 | 9500 | |
Laufgewicht (Kg) | 5370 | 5710 | 6150 | 6390 | 6630 | 6880 | 7220 | 7570 | 9360 | 10200 | 10800 | |
Parameter Für Die Wärmerückgewinnung | ||||||||||||
Kältemittelfüllung (kg) | 196 | 214 | 230 | 240 | 280 | 308 | 328 | 370 | 456 | 532 | 612 | |
Volumen Der Zurückgewonnenen Wärme | KW | 215 | 239 | 254 | 266 | 309 | 339 | 365 | 407 | 510 | 600 | 670 |
USRT | 61, 2 | 67, 8 | 72, 2 | 75, 6 | 87, 9 | 96, 5 | 103, 6 | 115, 7 | 144, 9 | 170, 6 | 190, 5 | |
X1000 Kcal/h | 185, 2 | 205, 1 | 218, 5 | 228, 5 | 265, 7 | 291, 7 | 313, 4 | 349, 8 | 438, 3 | 515, 9 | 576, 0 | |
Wärmerücksteller | Gehäuse - und Rohrtyp | |||||||||||
Max . Druck Auf der Wasserseite (MPa) | 1 | |||||||||||
Durchmesser Rohr Zu Wärmerücksteller (Zoll) | 3 Zoll | 3 Zoll | 3 Zoll | 3 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 4 Zoll | 5 Zoll | 5 Zoll | 5 Zoll | |
Rücklaufwasserstrom (m3/h) | 37, 0 | 41, 0 | 43, 7 | 45, 7 | 53, 1 | 58, 3 | 62, 7 | 70, 0 | 87, 7 | 103, 2 | 115, 2 | |
Wärmerückgewinnungseinheit Wasser Druckabfall (kPa) |
34 | 35 | 38 | 38 | 39 | 42 | 43 | 43 | 43 | 43 | 43 | |
Gesamtgewicht (kg) | 4340 | 4970 | 5460 | 5950 | 6470 | 6990 | 7350 | 7600 | 8450 | 9380 | 9980 | |
Laufgewicht (Kg) | 5520 | 6290 | 6580 | 6840 | 7190 | 7540 | 8020 | 8270 | 9620 | 10580 | 11200 |
Lieferanten mit verifizierten Geschäftslizenzen